ESM-ES301P (Sip. No. 090057)

Contact expansion ESM-ES.., 3 safety contacts, 1 auxiliary contact, cat. 4

  • Use up to category 4 according to EN ISO 13849-1
  • LED status indicators
  • Control using safety basic modules
  • 3 redundant safety contacts
  • 1 auxiliary contact (monitoring contact)
  • Earth fault/ground fault monitoring can be selected
  • plug-in connection terminals
ESM-ES301P (Sip. No. 090057)

Açıklama

Relay outputs

The outputs are electrically decoupled and of redundant design.

Connection

By using suitable wiring the following function can be selected:

  • Earth fault/ground fault monitoring to detect short circuits between the connecting cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram

Dimensional drawings

Dimensional drawings

Connection examples

Connection examples

Teknik Veriler

Approvals

c_UL_us_E155795_4/1CCC2024010305659956_ESM

Operating and display elements

LED display 2 status displays (green) for relays K1 and K2

Electrical connection values

Power consumption
at 24 V DC 1.2 W
Connection cross section 0.14 ... 2.5 mm² (Connection terminals (size))
Outputs
NumberTypeFunctionFootnote
1Signal Contact Configuration(Normally Closed Contact (Monitoring Contact for Base Unit))
3Relay contacts, floating and positively driven (redundant)Safety contacts 13/14, 23/24, 33/34(Normally open contact)
Rated insulation voltage Ui 250 V
Rated supply frequency 50 ... 60 Hz
Rated impulse voltage Uimp 4 kV
Operating voltage
AC/DC 24 V -10% ... +10% (All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent insulation measures.)
Test voltage
Control voltage / contacts 2.5 kV
Control voltage
to S11 DC 24 V
Control current
S11...S14 40 mA
Over voltage category III
Reverse polarity protection
On version UB =24V DC
Degree of contamination (external, according to EN 60947-1) 2
Safety contacts 13/14, 23/24, 33/34
Output type Relay contacts, floating and positively driven (redundant)
Cumulative current max. 10.5 A for all contacts

Mechanical values and environment

Connection type plug-in connection terminals
Storage temperature -25 ... 70 °C
Control cable length
with conductor cross-section 0.75 mm2 1000 m
Mechanical life
operating cycles 10 x 10⁶
Mounting type Mounting rail TH 35 (EN IEC 60715)
Degree of protection IP20
Ambient temperature
For UB = 24V AC -15 ... 40 °C (60°C at 24 V DC)
Material
Housing Polyamide PA6.6
Contact AgNi

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

PLMaximum SILPFHDCategoryMission time
Evaluating safety signalsPL e-1.2x10-8420 y
Only applies with switching voltage 24V DC and switching current up to 0.1 A (max. switching cycles 400,000 1/y) OR up to 1 A (max. switching cycles 73,000 1/y) OR up to 2 A (max. switching cycles 17,000 1/y)


Miscellaneous

in compliance with siehe Konformitätserklärung

İndirme

Komple paket

Tüm önemli belgeleri tek bir tıklama ile indirin.

İçerik:

  • Kullanım talimatları ve kullanım talimatlarına veya kısa talimatlara yapılan tüm eklemeler
  • Kullanım talimatlarını tamamlayan tüm veri sayfaları
  • Uygunluk beyanı
Paketin tamamını indirin (ZIP, 1,2 MB)

Tek Belgeler

Diğer Belgeler

Sipariş verileri

Sip. No. 090057
Makale adı ESM-ES301P
Ağırlık 0,2kg
Gümrük sınıfı 85364110
ECLASS 11.0 27-37-18-19 Device for monitoring of safety-related circuits