ESM-BA701 (Sip. No. 097224)

Basic module ESM-BA7.., 7 safety contacts, 4 auxiliary contacts, 2 monitoring contacts, cat. 4

  • ESM-BA.. Use up to category 4 according to EN ISO 13849-1
  • LED status indicators
  • 1-channel or 2-channel control
  • 7 redundant safety contacts
  • 4 auxiliary contacts
  • 2 monitoring contacts
  • Short circuit and earth fault/ground fault monitoring optional
ESM-BA701 (Sip. No. 097224)

Açıklama

Relay outputs

The outputs are electrically decoupled and of redundant design.

Connection options

By using suitable wiring, the following functions can be selected:

  • Relay start with automatic start or a start button.
  • Monitoring of downstream relays or contactors.
  • Simultaneity monitoring to monitor safety components over time.
  • Relay start using a monitored start button.
  • Short circuit monitoring to detect short circuits between the connecting cables and to shut down the outputs or prevent relay starting if necessary.
  • Earth fault/ground fault monitoring to detect short circuits between the connecting cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.

Auxiliary contacts

The relays in the series ESM‑BA7 are available with electrically separate normally closed contacts and auxiliary contacts.

Connection terminals

Optionally, the ESM-BA... devices are also available as versions with plug-in connection terminals.

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram

Dimensional drawings

Dimensional drawings

Connection examples

Connection examples

Teknik Veriler

Approvals

c_UL_us_E155795_4/1TÜV Rheinland_01/205/5114.03/24CCC2024010305659956_ESM

Operating and display elements

LED display 1 operating voltage status display (Pwr), 2 status displays (green) for relays K1 and K2

Electrical connection values

Power consumption
at 24 V DC 4.5 W
Power consumption (apparent power)
at 24 V AC 8.5 VA
Connection cross section 0.14 ... 2.5 mm² (Connection terminals (size))
Outputs
NumberTypeFunctionFootnote
2Transistor auxiliary contactsMonitoring Outputs O1 / O2
4Relay contacts, floatingAuxiliary contacts 81/82, 91/92, 101/102, 101/112(Normally closed monitoring contact)
7Relay contacts, floating and positively driven (redundant)Safety contacts 13/14, 23/24, 33/34, 43/44, 53/54, 63/64, 73/74(Normally open contact)
Rated insulation voltage Ui 250 V
Rated supply frequency 50 ... 60 Hz
Rated impulse voltage Uimp 4 kV
Operating voltage
AC/DC 24 V -10% ... +10% (All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent insulation measures.)
Test voltage
Control voltage / contacts 2.5 kV
Control voltage
to S11 DC 24 V
Control current
S11...S14 250 mA
Over voltage category III
Reverse polarity protection
on version UB=24V DC
Degree of contamination (external, according to EN 60947-1) 2
Monitoring Outputs O1 / O2
Output type Transistor auxiliary contacts
Output voltage 24 V DC
Output current max. 30 mA
Auxiliary contacts 81/82, 91/92, 101/102, 101/112
Output type Relay contacts, dry contacts
Safety contacts 13/14, 23/24, 33/34, 43/44, 53/54, 63/64, 73/74
Output type Relay contacts, floating and positively driven (redundant)
Cumulative current max. 35 A for all contacts at 40 °C (With a 10-mm spacing between enclosures, 20 A units arranged leak-proof.)

Mechanical values and environment

Connection type Connection terminals
Storage temperature -25 ... 70 °C
Control cable length
with conductor cross-section 0.75 mm2 1000 m
Mechanical life
operating cycles 10 x 10⁶
Mounting type Mounting rail TH 35 (EN IEC 60715)
Degree of protection IP20
Ambient temperature -15 ... 40 °C
Material
Housing Polyamide PA6.6
Contact AgSnO2

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

PLMaximum SILPFHDCategoryMission time
Evaluating safety signalsPL e-2.47x10-8420 y
Only applies with switching voltage 24V DC and switching current up to 0.1 A (max. switching cycles 500,000 1/y) OR up to 1 A (max. switching cycles 350,000 1/y) OR up to 2 A (max. switching cycles 100,000 1/y)


Miscellaneous

in compliance with siehe Konformitätserklärung

İndirme

Komple paket

Tüm önemli belgeleri tek bir tıklama ile indirin.

İçerik:

  • Kullanım talimatları ve kullanım talimatlarına veya kısa talimatlara yapılan tüm eklemeler
  • Kullanım talimatlarını tamamlayan tüm veri sayfaları
  • Uygunluk beyanı
Paketin tamamını indirin (ZIP, 1,3 MB)

Tek Belgeler

Diğer Belgeler

Sipariş verileri

Sip. No. 097224
Makale adı ESM-BA701
Ağırlık 0,405kg
Global Trade Item Number (GTIN) 4047048006669
Gümrük sınıfı 85364110
ECLASS 11.0 27-37-18-19 Device for monitoring of safety-related circuits