| Features |
- Two redundant relay outputs (safety outputs) with internally
monitored contacts
- Self-test without need to open the protective device
- Removable keyed terminal blocks – help avoiding
errors during servicing
- Actuator and read head in compact design (rectangular-shaped
or cylindrical)
|
Teach-in function of the evaluation unit
Prior to the system forming a functional unit, the actuator must
be allocated to the evaluation unit in a learn function. During
a learning process, the safety outputs are open and the door signal
output is at LOW, i.e. the system is in a safe condition. Repeated
learning by the same actuator on the same evaluation unit is not
possible. The number of learning procedures on one evaluation
unit is limited to a maximum of 8. The evaluation unit can only
be operated with the last actuator learnt.
Self-test without need to open the protective device
By applying 24 V DC to the test input TST, opening of the protective
device can be simulated. The safety outputs are switched off thus
enabling testing of the complete safety circuit. The diagnostic
output ERR of the evaluation unit is also set at HIGH as a monitoring
function. When resetting the test input TST, the evaluation unit
resets the diagnostic output ERR to LOW, the red LED switches
off and the safety outputs are switched on again. This permits
self-testing of the safety system without opening the protective
device.
Two redundant relay outputs with internally monitored contacts
|